Performance characteristics:
1. Three innovative variable flow technologies: W / A / R (Water, Air, Refrigerant) are used to overcome the weaknesses of circulating products, improve the equipment's low thermal efficiency in cold conditions, and solve high temperature conditions The two major problems of easy overload operation of the lower compressor ensure the water temperature is constant and durable;
2. The application of W / A / R variable flow technology makes the unit lower in noise and vibration during operation;
3. The new SAC refrigerant circuit technology effectively solves the precise distribution of energy supply in part load and achieves the lowest system operating cost;
4. Fast defrosting technology makes the unit run well in low temperature and humid environment.
model
KFXRS-7I
KFXRS-11I
KFXRS-19II
Power supply form
V/Hz
220V50Hz
220V50Hz
380V3N50Hz
Protection against electric shock
/
Class I
Class I
Class I
Outer protection level
/
IPX4
IPX4
IPX4
Rated heating capacity
KW
6.8
11.0
19.0
Rated power consumption
KW
1.75
2.7
4.35
Rated working current
A
8.2
12.3
7.7
Maximum power consumption
KW
2.6
4.0
6.40
Maximum working current
A
12.3
7.8
11.0
Rated water temperature
55
55
55
Maximum water temperature
60
60
60
Rated water production
L/h
160
240
400
Circulating water production
m/h
1.5
2.5
3.5
Water side flow resistance
Kpa
45
75
55
Exhaust side pressure
Mpa
3.0
3.0
3.0
Minimum suction side pressure
Mpa
0.05
0.05
0.05
Circulating water pipe diameter
DN
20
20
32
Refrigerant / charge
--/kg
R22/1.3
R22/1.8
R22/3.5
noise
Db(A)
55
55
60
Dimensions(LWH)
mm
680600820
680670845
8008001120
Unit weight
kg
73
135
175
Application environment range
-743
-743
-743
Remarks
1. Test conditions: dry bulb temperature 20 , wet bulb temperature 15 , initial water temperature 15 , termination water temperature 55 ;
2. Models, parameters, and performance may change due to product improvements without notice. Specific parameters please refer to the product nameplate.